E/S De Commande - Vacon nx Serie Manuel De L'applicatif

Masquer les pouces Voir aussi pour nx Serie:
Table des Matières

Publicité

VACON · 48
3.2

E/S DE COMMANDE

Reference potentiometer,
1-10kΩ
Remote Reference
0(4) - 20 mA
mA
READY
RUN
Fig. 7: Applicatif de commande local/distance – Configuration des E/S par défaut
3
OPTA1
Terminal
+10 V
Reference output
1
ref
Analogue input 1
AI1+
Voltage range 0—10V DC
2
Programmable (P2.1.12)
AI1-
I/O Ground
3
Analogue input 2
AI2+
4
Current range
0—20mA
Programmable
AI2-
5
(P2.1.11)
+24V
Control voltage output
6
GND
7
I/O ground
Place A: Start forward
DIN1
8
Programmable logic (P2.2.1)
Place A: Start reverse
9
DIN2
Ri min = 5 kohm
External fault input
DIN3
10
Programmable (P2.2.2)
11
CMA
Common for DIN 1—DIN 3
+24 V
12
Control voltage output
GND
13
I/O ground
Place B: Start forward
14
DIN4
Programmable logic (P2.2.15)
Place B: Start reverse
15
DIN5
Ri min = 5 kΩ
16
DIN6
Place A/B selection
17
CMB
Common for DIN4—DIN6
18
AO1+
Analogue output 1
Output frequency
Programmable (P2.3.2)
19
AO1-
Digital output
20
DO1
READY
Programmable (P2.3.7)
OPTA2 / OPTA3 *)
21
R O1
22
R O1
23
R O1
24
R O2
25
R O2
26
R O2
APPLICATIF DE COMMANDE LOCAL/DISTANCE
Signal
Description
Voltage for potentiometer, etc.
Analogue input 1
reference for place B
Ground for reference
and controls
Analogue input 2
reference for place A
Voltage for switches,
etc. max 0.1 A
Ground for reference and controls
Contact closed = start forward
Contact closed = start reverse
Contact open = no fault
Contact closed = fault
Connect to GND or +24 V
Voltage for switches (see #6)
Ground for reference and controls
Contact closed
= start forward
Contact closed
= start reverse
Contact open = place A is active
Contact closed = Place B is active
Connect to GND or +24 V
Range 0—20 mA/R
max. 500 Ω
Open collector,
I≤50 mA, U≤48 VDC
Relay output 1
RUN
Programmable
(P2.3.8)
Relay output 2
FAULT
Programmable
(P2.3.9)
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
,