Lenze Tmd Serie Instructions De Mise En Service page 20

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Code
No.
Name
7
Configuration TRIP
reset (error reset)
7
Auto-TRIP reset delay
7
Input voltage selection
7
Operating time counter
7
Mains connection time
counter
S-ramp integration
time
Skip frequency 1
Skip frequency 2
Skip frequency
bandwidth
LECOM power up
state
Serial time-out action
Serial fault time
Possible Settings
Lenze Selection
0
0
TRIP reset after LOW-HIGH change at
terminal 28, mains switching, or after
LOW-HIGH change at digital input
"TRIP reset"
1
Auto-TRIP reset
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel!
Automatic starting/restarting should only be used on equipment that is inaccessible to
personnel.
0.0
0.0
{s}
0
Low (for 200 or 400 V input)
1
High (for 230 or 480 V input)
Display
Total time in status "Start"
Display
Total time of mains = on
0.0
0.0
{s}
0.0
0.0
{Hz}
0.0
0.0
{Hz}
0.0
0.0
{Hz}
Note
Bandwidth (Hz) = fs (Hz) + L28 (Hz)
Example: L25 = 18 Hz and L28 = 4 Hz; the bandwidth = 18...22 Hz
0
0
Quick stop
1
Inhibit
0
Not active
0
1
Inhibit
2
Quick stop
3
Trip fault
50
50
{ms}
ENGLISH
Commissioning
• Auto-TRIP reset after the time set in c71
• More than 8 errors in 10 minutes will
trigger
60.0
See c70
• Lenze setting depends on C93
• During commissioning, confirm
correct setting based on mains voltage
0...999 h: format xxx
1000...9999 h: format x.xx (x1000)
10000...99999 h: format xx.x (x1000)
50.0
• c82 = 0.0: Linear accel/decel ramp
• c82 > 0.0: Adjusts S-ramp curve for
smoother ramp
240
• L25 and L26 define the start of the skip
range
240
• L28 defines the bandwidth of the skip
range
10.0
fs = L25 or L26
Selects controller reaction to serial timeout
65535
Sets the serial timeout length
IMPORTANT
S
fault
19

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Tmd001

Table des Matières