Installation
3.2

Electrical installation

3.2.1

Installation according to EMC requirements

EMC
Compliance with EN 61800-3/A11
Noise emission
Compliance with limit value class A according to EN 55011 if installed in a control
cabinet with the appropriate footprint filter and the motor cable length does not exceed
10m
A Screen clamps
B Control cable
C Low-capacitance motor cable
(core/core < 75 pF/m, core/screen < 150 pF/m)
D Electrically conductive mounting plate
E Filter
3.2.2

Fuses/cable cross-sections

Type
ETMD371L2YXA, ETMD551L2YXA
ETMD751L2YXA
1/N/PE
ETMD112L2YXA
ETMD152L2YXA
ETMD222L2YXA
ETMD371L2YXA...ETMD112L2_XA
ETMD152L2_XA
(4)
ETMD222L2_XA
(4)
ETMD402L2TXA
ETMD552L2TXA
3/PE
ETMD752L2TXA
ETMD371L4TXA...ETMD222L4TXA
ETMD302L4TXA
ETMD402L4TXA
ETMD552L4TXA
ETMD752L4TXA
(1) Observe the applicable local regulations
(2) Pulse-current or universal-current sensitive earth leakage circuit breaker
(3) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS, or equivalent
(4) "_" = Y or T; the ratings are the same for either model with 3/PE input
8
(1)
Installation to EN 60204-1
Miniature
L1, L2, L3, PE
Fuse
circuit
breaker
M10 A
C10 A
M16 A
C16 A
M20 A
C20 A
M25 A
C25 A
M30 A
C30 A
(4)
M10 A
C10 A
M16 A
C16 A
M16 A
C16 A
M25 A
C25 A
M40 A
C40 A
M50 A
C50 A
M10 A
C10 A
M16 A
C16 A
M16 A
C16 A
M20 A
C20 A
M25 A
C25 A
ENGLISH
B
Installation to UL
L1, L2, L3, PE
Fuse
(3)
[mm²]
[AWG]
1.5
10 A
14
2.5
15 A
14
2.5
15 A
12
2.5
20 A
12
4.0
30 A
10
1.5
10 A
14
1.5
12 A
14
2.5
15 A
12
4.0
25 A
10
6.0
35 A
10
45 A
1.5
10 A
14
1.5
12 A
14
2.5
15 A
14
2.5
20 A
12
4.0
25 A
10
E
C
D
A
Tmd005
E.l.c.b.
(2)
> 30 mA
8
8