3.4 Outputs

Output for the proportional valve
Output transistor
Load current
Output voltage
Clock frequency
Number of outputs
To regulate the Type 2832 proportional vlave, the controller outputs a current-regu-
lated PWM signal via a transistor.
Output for the control of the vaccum pump motor
Output transistor
Load current
Output voltage
Special freatures
Number of outputs
The „open-collector" output shown in Figure 4 is used for the control of a relay/con-
tactor for switching the vacuum pump motor.
The „open-collector" output is switched active by the controller as long as the propor-
tional valve is open.
from CPU
(Port Bx)
Figure 4: "Open-Collector" transistor output to the pump controller
8 - 1094
Positiv-switching transistor
0 to 250 mA
24 V DC
270 Hz
One valve output each for + and -
„Open-Collector" transistor output
100 mA
24 V DC
Freewheeling diode, after-run time adjustable (in con-
nection with the manual control unit Type MKNE-1094)
One pump output each for + (24 V) and – (GND)
2.2 k
BC 337 or similar
10 k
+ 24 V
Output