10.3.3. function of the DiP switches
dip
function
switches
1
ON
Reversal of the effective direction of the set-point
value (set-point value 20 – 4 mA corresponds to
position 0 – 100 %), descending (DIR.CMD)
OFF
Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position
0 – 100 %), ascending
2
ON
Sealing function active. The valve completely closes
below 2 %
and opens above 98 % of the set-point
12)
value (CUTOFF)
OFF
No sealing function
3
ON
Correction characteristic for adjustment of the oper-
ating characteristic (linearization of the process char-
acteristic CHARACT)
OFF
Linear characteristic
4
ON
Operating status MANUAL (MANU)
OFF
Operating status AUTOMATIC (AUTO)
Tab. 10: DIP switches
Can be changed via communications software.
12)
Type 8694
Start-up
on
dip
1 2 3 4
12)
10.3.4. Display of the leDs
ON
DIP
1 2 3 4
Fig. 17: Display of the LEDs
LED 1
Display of
AUTO, MANU, X.TUNE and FAULT
(green / red)
LED 2
Display of state of actuator
(open, closed, opens or closes)
(green / yellow)