Burkert 8694 Guide Rapide page 17

Masquer les pouces Voir aussi pour 8694:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Electrical installation
9.2.1. e lectrical installation with cable gland
procedure:
The screw-type terminals can be accessed by unscrewing the
body casing (stainless steel).
Push the cables through the cable gland.
Connect the wires.
1
2
2)
3
2)
4
5
6
7
Fig. 9:
Screw-type terminals
terminal
configuration
1
Binary input +
2
Analogue position feedback +
2)
3
Analogue position feedback GND
2)
4
Set-point value +
5
Set-point value GND
6
Supply voltage +
7
Supply voltage
Tab. 3:
Electrical installation with cable gland
only optional
2)
Type 8694
(0/4 - 20 mA)
24 V DC
GND
Seal
Body casing
Fig. 10: Position of the seal in the body casing
Check that the seal is correctly positioned in the body casing.
note!
damage or malfunction due to penetration of dirt and humidity!
To ensure protection class IP65 / IP67:
• Tighten the union nut on the cable gland according to the cable
size or dummy plugs used (approx. 1.5 Nm).
• Screw the body casing in all the way.
Tighten union nut on the cable gland (torque approx. 1.5 Nm).
Close the device (assembly tool: 674077
When the supply voltage is applied, the positioner is operating.
Actuate the automatic adjustment of the positioner, as described
in the chapter entitled "10.2. Automatic adjustment X.TUNE".
The assembly tool (674077) is available from your Bürkert sales office.
3)
english
Body casing
).
3)
17

Publicité

Table des Matières