Safety Positions - Burkert 8694 Guide Rapide

Masquer les pouces Voir aussi pour 8694:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

led 1 (green / red)
LeD States
Display
green
red
on
off
Acceleration phase when Power ON
flashes slowly
off
Operating status AUTO (AUTOMATIC)
flashing
flashing
MANUAL operating status
alternating
flashes quickly
off
X.TUNE function
off
on
ERROR (see operating instructions)
flashing
flashing AUTO operating status for sensor break
detection
slow
Tab. 11: Display LED 1
led 2 (green / yellow)
LeD States
Display
green
yellow
on
off
Actuator closed
off
on
Actuator open
flashes
Remaining control deviation
off
slowly
(actual value > set-point value)
flashes
Remaining control deviation
off
slowly
(actual value < set-point value)
flashes
off
Closing in MANUAL operating status
quickly
flashes
off
Opening in MANUAL operating status
quickly
Tab. 12: Display LED 2
24
english
Type 8694
Safety Positions
11. safeTy PosiTions
actuator
designation
system
single-acting
Control
up
function A
down
single-acting
Control
up
function B
down
Tab. 13: Safety positions
safety positions after
failure of the auxiliary
power
electrical
pneumatic
pilot-controlled
control system:
down
down
direct-acting
control system:
not defined
pilot-controlled
control system:
up
up
direct-acting
control system:
not defined