Resistance transmitters
Table 7-2
Measured variable: Ohmic resistance
Input type
Characteristic
Unit of measurement
Measuring range
Resistance
Resistance
Thermocouples
Table 7-3
Measured variable: Temperature
Sensor type (thermo pairs)
● Type B
Pt30Rh-Pt6Rh according to DIN IEC 584
● Type C
W5%-Re according to ASTM 988
● Type D
W3%-Re according to ASTM 998
● Type E
NiCr-CuNi according to DIN IEC 584
● Type J
Fe-CuNi according to DIN IEC 584
● Type K
NiCr-Ni according to DIN IEC 584
● Type L
Fe-CuNi according to DIN 43710
● Type N
NiCrSi-NiSi according to DIN IEC 584
● Type R
Pt13Rh-Pt according to DIN IEC 584
● Type S
Pt10Rh-Pt according to DIN IEC 584
● Type T
Cu-CuNi according to DIN IEC 584
● Type U
Cu-CuNi according to DIN 43710
Cold junction compensation
● Internal
● External
● External fixed
SITRANS TH/TR/TF
A5E32363963-02, 09/2021
SITRANS TH200/TH300, TR200/TR300
Resistance, potentiometer
Linear to resistance or special characteristic curve
Ω
Range
0 ... 390
0 ... 2200
SITRANS TH200/TH300, TR200/TR300
Range
+100 ... +1820
(212 ... 3308)
0 ... +2300
(32 ... 4172)
0 ... +2300
(32 ... 4172)
-200 ... +1000
(-328 ... +1832)
-210 ... +1200
(-346 ... +2192)
-230 ... +1370
(-382 ... +2498)
-200 ... +900
(-328 ... +1652)
-200 ... +1300
(-328 ... +2372)
-50 ... +1760
(-58 ... +3200)
-50 ... +1760
(-58 ... +3200)
-200 ... +400
(-328 ... +752)
-200 ... +600
(-328 ... +1112)
With integrated resistance thermometer Pt100
With external Pt100 IEC 60751 (two-wire or three-wire connection)
Cold junction temperature can be set as fixed value
Min. span
5
25
Min. span
100 (180)
100 (180)
100 (180)
50 (90)
50 (90)
50 (90)
50 (90)
50 (90)
100 (180)
100 (180)
40 (72)
50 (90)
SITRANS TH400
Range
-
0 ... 10000
SITRANS TH400
Range
+400 ... +1820
(752 ... 3308)
0 ... +2300
(32 ... 4172)
0 ... +2300
(32 ... 4172)
-100 ... +1000
(-148 ... +1832)
-100 ... +1000
(-148 ... +1832)
-100 ... +1200
(-148 ... +2192)
-200 ... +900
(-328 ... +1652)
-180 ... +1300
(-292 ... +2372)
-50 ... +1760
(-58 ... +3200)
-50 ... +1760
(-58 ... +3200)
-200 ... +400
(-328 ... +752)
-200 ... +600
(-328 ... +1112)