koban KPAW-01 Manuel page 150

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Blue
1. Insert red test leads to L1, L3 input terminal.
2. Insert black test leads to COM input terminal and connect
it to the neutrual wire of the 3 phase.
3. Jump over the second phase measurement.
4. The first and the third phase measuring method is same
as 3 phase 4 wires.
In figure 15 ∑W = W2 + W3.
NOTE
It can only sum up the current measurement value. The
maximum and minimum value cannot be summed up.
Only at KW range can carry out sum of watts
measurement, other ranges cannot carry out this
measurement.
When testing has been completed, disconnect the
connection between the testing leads and the circuit under
test and remove testing leads from the input terminals.
www.grupotemper.com
TRUE RMS 1000A AC WATT Clamp Meter
Figure 15
KPAW-01
Yellow
Red
25

Publicité

Table des Matières
loading

Table des Matières