Power Connections

Compare this illustration with the generator to familiarize yourself with the location of these connections.
A - Power Connection - Power connection to transfer switch.
B - Neutral Connection - Connect to transfer switch neutral.
C - Ground Connection - Connect to transfer switch ground.
Ground the generator per applicable codes, standards, and
regulations. There are two generator GND lug locations.
The location shown by (C, above) should suffice for most
applications. The second generator GND lug is located
on the frame. This should ONLY be used for a ground rod
located at the generator, if required by local codes.
For system connections such as remote start, e-stops,
and controller inputs and outputs, refer to the connection
diagrams on the following pages.
B
C
A
• For power output connection, use 75°C (167°F) wire
rated for ambient temperature of 40°C (104°F) per
NEC Tables 310.15(B)(16) and 310.15(B)(2)(a).
• For utility circuit connection, use #14 AWG minimum
600 volt, 167-194°F (75-90°C) wire.
• For transfer switch communication, use #18 AWG
twisted pair conductors, no greater than 200 ft (60 m)
in length, 600 volt, 167-194°F (75-90°C) wire.