Technical Data
11-18
Various measures can be taken to afford protection against
condensation:
1. Temperature control is recommended for this purpose (see Fig.
11-3). The water temperature is controlled as a function of room
temperature. This method is certainly to be preferred where there
are high room temperatures, low water temperatures and high
humidities.
2. Physical dehumidifying. This is only effective in closed rooms. It
comprises operating an air/water heat exchanger with cold water to
constantly condense the moisture out of the room air.
3. A humidity alarm can be installed to give a warning when
condensation is imminent. Such an alarm is available from
ENDRICH (www.endrich.com); when the temperature falls to within
2 K of dew point, a signal contact closes.
6SE7087-7JK50
Operating Instructions
SIMOVERT MASTERDRIVES
08.2008
Siemens AG