Type K:
X9 - external
DC 24 V supply,
main contactor
control
5
4
3
2
1
NOTE
WARNING
Siemens AG
6SE7087-7JK50
SIMOVERT MASTERDRIVES
The 5-pole terminal strip is used for connecting up a 24 V voltage
supply and a main or bypass contactor.
The connection base is easily accessibly located on the DIN rail below
the slide-in unit of the electronics box.
The voltage supply is required if the inverter is connected up via a main
or bypass contactor.
The connections for the contactor control are floating.
Terminal
Designation
5
Main contactor control
4
Main contactor control
3
n.c.
2
0 V
1
+24 V (in)
Connectable cross-section: 2.5 mm² (AWG 12)
Table 7-4
Connection of external DC 24 V aux. voltage supply and main contactor
control (Type K)
The excitation coil of the main contactor has to be damped with
overvoltage limiters, e.g. RC element.
The 230 V fan has to be supplied with AC230 V externally. The
connecting points are located on the fuse-disconnectors on the right
next to the DIN rail of X9.
The external 24 V voltage supply has to meet the requirements of safe
electrical isolation (PELV current circuit = Protective Extra Low
Voltage).
Operating Instructions
Meaning
Main contactor control
Main contactor control
Not connected
Reference potential
24 V voltage supply
Connecting-up
Range
AC 230 V
1 kVA
0 V
For current
requirement
see section
"Technical
Data"
7-9