IMPORTANT: In mobile home installations, gas dryers
MUST be permanently attached to the floor at the time
of installation. Order No. 526P3 Hold Down Kit (availa-
ble at extra cost) for a manufactured (mobile) home in-
stallation. Follow the instructions supplied with the kit.
Installation of unit must conform to the Manufactured Home
Construction and Safety Standards, Title 24 CF4, Part 32-80 or
Standard CAN/CSA-Z240 MH.

Connect Dryer Exhaust System

To reduce the risk of fire and combustion gas accu-
mulation the dryer MUST be exhausted to the out-
doors.
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
Description
Dryer sides and rear clearance
Dryer top clearance
Dryer front clearance
Exhaust duct clearance to com-
bustible material
Weather hood to ground clear-
ance
Distance from floor or ceiling
to air opening edge
Area of centered air openings
in closet door. Louvered door
with equivalent air openings is
acceptable. (Minimum clearan-
ces are shown.)
For new installations, locate
top of wall vent 1067 mm [42
inches] above floor to make
venting easier to connect.
Rear clearance is minimum. 51 mm [2 inches] is recommended for utility connection. 152 mm [6
inches] is recommended when venting through rear of unit.
WARNING
Free Standing/Alcove In-
stallation
0 mm [0 in.]
305 mm [12 in.]
Not Applicable
51 mm [2 in.]
305 mm [12 in.]
Not Applicable
Not Applicable
1067 mm [42 in.]
Table 1
To reduce the risk of fire and the accumulation of
combustion gases, DO NOT exhaust dryer air into a
window well, gas vent, chimney or enclosed, unven-
tilated area, such as an attic, wall, ceiling, crawl
space under a building or concealed space of a
building.
This gas appliance contains or produces a chemical
or chemicals which can cause death or serious ill-
ness and which are known to the State of California
to cause cancer, birth defects, or other reproductive
W604
harm. To reduce the risk from substances in the fuel
or from fuel combustion, make sure this appliance is
installed, operated, and maintained according to the
instructions in this manual.
15
Closet Installation
0 mm [0 in.]
305 mm [12 in.]
51 mm [2 in.]
51 mm [2 in.]
305 mm [12 in.]
76 mm [3 in.]
1016 sq. mm/open [40 sq. in./
open]
1067 mm [42 in.]
WARNING
WARNING
Part No. D512681ENR9
Installation
W045
W115