Commissioning
Initial switch−on
Initial switch−on
)
Note!
Code C0356/x serves to set the times for cyclic transmission.
ƒ
The CAN master can access the Lenze codes saved to the controller via the
ƒ
index.
Index = 24575 ˘ Lenze code number (Cxxxx)
The controller is only ready for operation if a HIGH level is applied to
ƒ
terminal 28 of the function module (controller enable via terminal).
– Please observe that the controller can be inhibited through various
sources. All sources act like a series connection of switches.
– If the drive does not start in spite of the controller enable via terminal
28, check whether the controller is still inhibited via another source such
as the s key of the keypad.
Step
Description
1.
Configure master system (CAN master) for communication with the function module.
2.
Inhibit standard device via terminal 28 (CINH).
l
Set terminal 28 to LOW level.
l
The standard device can be inhibited and enabled via the bus subsequently.
3.
Switch on the mains voltage.
l
The standard device will be ready for operation after approx. 1 second.
l
The controller inhibit is active.
Response of standard device
l
The green LED is blinking.
l
Keypad:
4.
C
Set node address via ...
– C0350 or
– DIP switch (if available).
(Lenze setting: 500 kbps)
A node address in a CAN network must not be used more than once.
D Set baud rate via ...
– C0351 or
– DIP switch (if available).
(Lenze setting: 1)
All CAN nodes must have an identical baud rate.
Changes will not be accepted until a "Reset node" command (C0358 = 1) has been
executed.