Initial switch−on
)
Note!
The standard device is only ready for operation if a HIGH level is applied to
ƒ
terminal 28 (controller enable via terminal).
– Please note that the controller can be inhibited by various sources. The
sources act like a series connection of switches.
– If the drive does not start even though the controller has been enabled
via terminal 28, check whether the controller has been inhibited by
another source. Another source could be the s key of the XT keypad.
Please note the different status information for code C0068 compared to
ƒ
software version "0.1" (see the following table).
Bit
Function
8
RFR (controller enable)
11
IMP (pulse inhibit)
15
TRIP (fault)
EDK82ZAFLC−001 DE/EN/FR 6.0
Description
0: no controller enable
1: controller enable
0: pulses for power sections inhibited
1: pulses for power sections enabled
0: no fault
1: fault exists
l
Commissioning
Initial switch−on
7
51

Publicité