8
Diagnostics

LED status displays

Pos.
Colour
1
yellow
2
green
1
2
yellow /
+
green
EDK82ZAFLC−001 DE/EN/FR 6.0
Status
Description
off
l
No communication with the host system
l
The function module is not supplied with voltage.
blinking
Communication via the function module to the host system has been
established.
off
l
The function module is not supplied with voltage.
l
The standard device and/or the external voltage supply is/are
switched off.
blinking
The function module is supplied with voltage but is not connected to
the standard device.
Possible causes:
l
The standard device is switched off.
l
The standard device is in the initialisation phase.
l
The standard device is not available.
on
The function module is supplied with voltage and is connected to the
standard device.
blinking
Internal error of the function module
l
Diagnostics