Factory settings
110
For the factory settings, see Tab. 12 below.
Menu
Designation
no.
1.0.0.0 Setpoints
2.0.0.0 Control mode
3.0.0.0 Δp-v gradient
2.3.3.0 Pump
4.3.1.0 Base-load pump
5.1.1.0 Operating mode
5.1.3.2 Internal/external pump
cycling
5.1.3.3 Pump cycling time interval
5.1.4.0 Pump enabled/disabled
5.1.5.0 SSM
5.1.6.0 SBM
5.1.7.0 External off
5.3.2.0 In1 (value range)
5.4.1.0 In2 active/inactive
5.4.2.0 In2 (value range)
5.5.0.0 PID parameter
5.6.1.0 HV/AC
5.6.2.0 Emergency operation speed
5.6.3.0 Auto reset time
5.7.1.0 Display orientation
5.7.2.0 Pressure value correction
5.7.6.0 SBM function
5.8.1.1 Pump kick active/inactive
5.8.1.2 Pump kick interval
5.8.1.3 Pump kick speed
Tab. 12: Factory settings
Factory-configured values
• Controller:
approx. 60% of n
pump
max
• Δp-c:
approx. 50% of H
pump
max
• Δp-v:
approx. 50% of H
pump
max
Δp-c activated
Lowest value
ON
MA
Main/standby mode
Internal
24 h
Enabled
Collective fault signal
Collective run signal
Collective external off
0–10 V active
OFF
0-10 V
See chapter 9.4 "Setting the con-
trol mode" on page 95
HV
approx. 60% of n
pump
max
300 s
Display on original orientation
Active
SBM: Run signal
ON
24 h
n
min