System-specific parameters
Sets the desired return set temperature when dynamic cooling is
selected. The return nominal value is adapted linear to the outside
temperature. A characteristic line is used for this purpose, which is
set at two specific operating points. The return nominal value is
determined at the fixed outside temperatures of 15 °C and 35 °C.
Sets the time programs for dynamic cooling.
Sets the times during which dynamic cooling is blocked.
For each weekday, it is possible to select whether time 1, time 2,
no time or both times are active for a block. Blocks that exceed a
weekday are activated or deactivated at the end of each day
accordingly.
Sets the room set temperature for silent cooling.
The actual value is measured by room climate station 1.
Settings to lower the heating characteristic curve of heating
circuit 2/3
Sets the times at which the lower process for
heating circuit 2/3 should take place.
Sets the temperature value by which the heating characteristic
curve for
heating circuit 2/3 is to be lowered by during a lower process.
For each weekday, it is possible to select whether time 1, time 2,
no time or both times are active when the temperature is lowered.
Operations to lower the fan speed that exceed a weekday are
activated or deactivated at the end of each day accordingly.
Settings to raise the heating characteristic curve of heating
circuit 2/3
Sets the times at which the raise process for
heating circuit 2/3 should take place.
Sets the temperature by which the heating characteristic curve
of heating circuit 2/3 is to be raised during a raise process.
For each weekday, it is possible to select whether time 1, time 2,
no time or both times are active during a raise. Operations to raise
the temperature that exceed a weekday are activated or
deactivated at the end of each day accordingly.
Sets the room set temperature for silent cooling. The actual value
is measured by room climate station 1/2.
Sets the desired domestic hot water set temperature.
Sets the time program for domestic hot water blocks.
Sets the times in which domestic hot water preparation is blocked.
For each weekday, it is possible to select whether time 1, time 2,
no time or both times are active for a block. Blocks that exceed a
weekday are activated or deactivated at the end of each day
accordingly.
Sets the domestic hot water set temperature which should be
maintained even during a domestic hot water block.
To carry out a thermal disinfection, the domestic hot water heating
takes place once to the desired temperature. The heating period is
terminated automatically when the set temperature is reached, at
12:00 p.m. or after 4 hours at the latest.
Sets the start time for the thermal disinfection.
452115.66.36 · FD 9709
Wärmepumpenmanager
Setting range
10 ... 15 °C ... 30
10 ... 15 °C ... 30
00:00 ... 23:59
00:00 ... 23:59
N / T1 / T2 / J
15.0 ... 20.0 °C ... 30.0
00:00 ... 23:59
00:00 ... 23:59
0 K ... 19
N / T1 / T2 / Y
00:00 ... 23:59
00:00 ... 23:59
0 K ... 19
N / T1 / T2 / Y
15.0 ... 20.0 °C ... 30.0
30 ... 50 °C ... 85
00:00 ... 23:59
00:00 ... 23:59
N / T1 / T2 / J
0 ... 10 ...
DHW set temp.
00:00 ... 23:59