3
Technical data
General data and operating conditions
Ambient conditions
Climatic conditions
Storage
Transport
Operation
Site altitude
Electrical
Mains connection AC system
Max. mains voltage range
E82MV251... and E82MV371...
E82MV551... to E82MV222...
E82MV302... to E82MV752...
Mains frequency
Mechanical
Vibration resistance
2
(9.81 m/s
= 1 g)
Mounting conditions
Mounting position
Free spacess
Dimensions,
Weights
86
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C)
IEC/EN 60721−3−2
2K3 (−25 ... +70 °C)
IEC/EN 60721−3−3
3K3 (−20 ... +60 °C)
At temperatures > +40 °C, reduce the rated output
current by 2.5 %/°C.
< 4000 m amsl
Reduce rated output current by 5 %/ 1000 m
above 1000 m amsl.
1/N/PE or 2/PE 180 V − 0 % ... 264 V + 0 %
3/PE 320 V − 0 % ... 550 V + 0 %
3/PE 320 V − 0 % ... 550 V + 0 %
45 Hz − 0 % ... 65 Hz + 0 %
Germanischer
acceleration resistant up to 2 g
Lloyd
l
General
conditions
All mounting positions and mounting alignments are permitted
Above:
100 mm
To the sides
100 mm
^
Chapter "Mechanical installation"
^
Chapter "Technical data", "Operation with rated power" or "Operation
with increased rated power"
l
EDK82MV371 DE/EN/FR 7.0

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E82mv 2b sérieE82ev251E82ev371E82mv251_2bE82mv371_2b

Table des Matières