Lenze 8200 motec Instructions De Montage page 85

Masquer les pouces Voir aussi pour 8200 motec:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EMC
Complies with requirements according to EN 61800−3
Noise emission
l
cable−guided
Noise immunity
Operation on public
supply systems
1)
The additional measures mentioned effect that solely the controllers meet the requirements of
EN 61000−3−2. The machine/system manufacturer is responsible for compliance with the
requirements of the machine/system!
EDK82MV371 DE/EN/FR 7.0
General data and operating conditions
IEC/EN 61800−3
Motor mounting:
Compliance with limit class C1
Wall mounting:
Requirements
Standard
ESD
IEC/EN 61000−4−2
Cable−guided high
IEC/EN 61000−4−6
frequency
Burst
IEC/EN 61000−4−4
Surge (surge
IEC/EN 61000−4−5
voltage on mains
cable)
EN 61000−3−2
Total power on the mains
0.25 kW ... 0.75 kW
> 1 kW
l
Technical data
– Compliance with the limit class C1 when shielded
motor cables up to a length of 1 m are used
– Compliance with the limit class C2 when shielded
motor cables up to a length of 10 m are used
Severity
8 kV with air discharge,
4 kV with contact discharge
150 kHz ... 80 MHz,
10 V/m 80 % AM (1 kHZ)
3/4, i.e. 2 kV / 5 kHz
3, i.e. 1.2 / 50 ms,
1 kV phase/phase, 2 kV
phase/PE
Limitation of harmonic
currents
Compliance with the
1)
requirements
With mains choke
No measures required
3
85