4
Mechanical installation
Motor mounting
EMC−compliant wiring
Conditions for trouble−free operation:
ƒ Except for the mains cable, use shielded cables only.
ƒ Carefully connect the shielding to PE.
ƒ Connect motor and mains PE conductors to separate PE terminals.
X1
A
Fig. 4−5
0
Mains cable L1, N, PE or L1, L2, PE
1
PE connection for mains cable
2
PE connection for motor
3
Shield connection, control cable ( fix the shield tightly to the sheet with the cable tie)
4
Shielded control cable
5
Function module
X1
Terminal strip mains connection
X2
Terminal strip motor connection
PES
HF shield connection by large surface connection to PE
100
B
F
l
Shield connection:
1. Prepare the cable
X2
2. Insert the cable tie
C
3. Lay the cable into the
D
cable tie and tighten it.
The shield must be
tightly connected to
the shield sheet.
E
8200mot151
EDK82MV371 DE/EN/FR 7.0