Commissioning
Important controller codes
Code
No.
Name
C0087 Rated motor
speed
C0088 Rated motor
current
C0089 Rated motor
frequency
C0090 Rated motor
voltage
C0091 Motor cos 
C0119
Configuratio
v
n of motor
temperature
monitoring
(PTC input) /
earth fault
detection
C0140
Additive
*
frequency
setpoint
(NSET1−NAD
D)
126
Possible settings
Lenze
Selection
à
300
à
0.0
50
10
à
50
à
0.40
0
0
PTC input
inactive
1
PTC input active,
TRIP effected
2
PTC input active,
warning effected
3
PTC input
inactive
4
PTC input active,
TRIP effected
5
PTC input active,
warning effected
0.00
−650.00
{1 rpm}
0.1 (A)
{1 Hz}
{1 V}
{0.1}
Earth fault
detection active
Earth fault
detection inactive
{0.02
Hz}
l
IMPORTANT
à
16000
Device−dependent
à
650.0
Device−dependent
0.0 ... 2.0 x rated output
current of the controller
960
à
500
230 V for 230 V
controllers,
400 V for 400 V
controllers
à
1.0
Device−dependent
l
Configure signal
output in C0415
l
If several parameter
sets are used,
monitoring has to be
set separately for
every parameter set.
l
Deactivate earth fault
detection if the earth
fault detection is
actuated
unintentionally.
l
If the earth fault
detection is activated,
the motor starts with
a delay of approx.
40 ms after controller
enable has been set.
Selection via j
650.00
l
function of the
keypad or parameter
channel
l
Acts additively on the
main setpoint
l
Value will be stored
when switching the
mains or removing
the keypad
l
C0140 is only
transferred during
parameter set
transfer with GDC
(not with keypad)
EDK82MV371 DE/EN/FR 7.0