Commissioning
Important controller codes
Code
No.
Name
C0517
User menu
*
v
1 Memory 1
2 Memory 2
3 Memory 3
4 Memory 4
5 Memory 5
6 Memory 6
7 Memory 7
8 Memory 8
9 Memory 9
10 Memory 10
C0608
Fan
*
monitoring
128
Possible settings
Lenze
Selection
50
C0050 Output frequency (MCTRL1−NOUT)
34
C0034 Range of analog setpoint selection
7
C0007 Fixed configuration of digital input
signals
10
C0010 Minimum output frequency
11
C0011 Maximum output frequency
12
C0012 Acceleration time main setpoint
13
C0013 Deceleration time main setpoint
15
C0015 V/f rated frequency
16
C0016 V
boost
min
2
C0002 Parameter set transfer
Possible entries for C0517
xxxx
All codes apart from the codes
labelled with "(A)".
0
0
Inactive
1
TRIP error message
2
Warning
l
IMPORTANT
l
After mains
switching or in the
g function the code
from C0517/1 is
displayed.
l
In the Lenze setting
the user menu
contains the most
important codes for
commissioning the
operating mode "V/f
characteristic control
with a linear
characteristic"
l
If the password
protection is active,
only the codes
entered in C0517 can
be freely accessed
l
If less than 10 codes
are required, assign
the value "0" (zero) to
the memory locations
not used. Please
observe that the
software
automatically assigns
code C0050 to a
memory location that
is not used, if it has
not been explicitly
assigned to another
memory location.
Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x =
cccc.ss
8200 motec 3 ... 7.5 kW:
Function must be
activated during
commissioning
(recommended: C0608 =
1)! Otherwise, the
controller may be
destroyed due to
overheating.
For all other controllers:
It is essential to set
C0608 = 0.