Technical Data; Safety Instructions - Eaton CROUSE-HINDS Série Mode D'emploi

Masquer les pouces Voir aussi pour CROUSE-HINDS Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2

Safety instructions

Target group:
For skilled electricians and suitable
qualified, instructed personnel in
accordance with national legislation,
including the relevant standards and, where
applicable, in acc. with IEC/EN 60079-14 on
electrical apparatus for explosive atmospheres.
The multiple plug and socket systems 7-pole
(GHG 511 .7. / GHG 592) and 21-pole (GHG
511 .9 / GHG 591) are not suited for use in
Zone 0.
The operations must be carried out by
electrical suitably trained in hazardous area
with knowledge of increased safety
explosion protection IEC/EN 60079-14.
The temperature class and type of
protection stated on the apparatus shall
be observed.
To ensure adherence to the temperature
class stated on the type label of the
apparatus, the permissible ambient
temperature, the rated terminal cross
section and the self-heating of the appara-
tus, that
is mainly due to the power dissipation, shall
be taken into account (test criterion for the
self-heating is an overload of 10%).
Modifications or changes to the plug and
socket systems are not permitted.
They shall be used for their intended
purpose and in a perfect and clean state.
Prior to being put into operation, the plug
and socket systems shall be checked in
accordance with the instructions as per
section 6.
The sockets may only be used with the
associated COOPER CROUSE-HINDS plugs
in undamaged condition.
The 7-pole wall socket is safeguarded by an
interlocking switch and can, therefore, not
be switched on if the plug is not inserted.
The plug of the 21-pole plug and socket may
not be inserted into the 21-pole sockets and
coupler or withdrawn from them while they
are live (see also section 5).
Before initial operation, any foreign matter
shall be removed from the apparatus.
The national safety rules and regulations
for the prevention of accidents, as well as
the safety instructions included in these
operating instructions, that, like this text,
are set in italics, shall be observed!
8
Explosion-protected plugs and sockets, 7-pole
GHG 511 .7 .. / 592 and 21-pole GHG 511 .9.. / 591
1

Technical data

1.1
Plugs and sockets, 7-pole
EC type examination certificate
Marking acc. to 2014/34/EU
and standard of series EN 60079:
Rated voltage
Max. rated current
Perm. short-circuit back-up fuse
Switching capacity AC 3
Switching capacity AC 15
Switching capacity DC 13
Permissible ambient temperature
(Other temperatures possible with special versions.)
Perm.storage temperature in original packing
Degree of protection to IEC/EN 60529
with closed and secured hinged cover as well as combinations properly plugged together
Insulation class acc. to IEC/EN 61140
Cable entries
Wall socket (GHG 511 47) 2 x M40
suitable cables and test torques of the
pressure screw
Seal 1+2
min.
1 2
3
max.
Seal 1
min.
1 2
3
max.
Test torque for screw in thread cable entry
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.
Plug (GHG 592 2)
Supply terminal
Switch contact block of wall socket
Pin for plug
Test torques
Cover- and plug screws
Terminals
Weight (standard version)
Dimensions in mm
Wall socket 7pole
Plug 7pole
Code 7pole
6h
5h
maize yel.
brown
orange
PTB 00 ATEX 1109
II 2 G Ex e IIC T5 / T6
II 2 G Ex de [ia] IIC T5 / T6
up to 400 V, 50/60 Hz
16 A (T6) / 20 A (T5)
without therm. protect. with therm. protect.
max. 16 A
400 V /16 A
400 V / 6 A
24 V / 6 A
-20° C up to +40° C (standard version)
-20° C up to +40° C
IP 66 (standard version)
I – with metal flange or metal cable entries
II - is complied with by devices
(standard version)
1x M40 + 1x screwed plug
Ø
19.0
(1)
22.0
22.0
(1)
28.0
7 .5 Nm
Ø 9 - 17 mm
Cross section
2 x 1.5 - 4.0 mm²
1 x 1.0 - 2.5 mm² *
* crimp or soldered connections
2.5 Nm
2.5 Nm
Wall socket
approx. 2.20 kg
Contact ararangement 7pole
7h
X = fixing dimensions
GB
max. 25 A gG
230 V / 8 A
230 V / 0.4 A
Nm
3.3
5.5
3.3
6.7
Stripped wire length
6 mm
13 mm
Plug
approx. 0.30 kg