Technical Data; Plug And Socket Ghg 514 - Eaton Crouse-Hinds GHG 514 Mode D'emploi

Fiche et prise de pour atmosphères explosives 63a, à 4 pôles et 5 pôles
Masquer les pouces Voir aussi pour Crouse-Hinds GHG 514:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Code Zone 1
3-pol. + PE
3-pol. + N + PE
Dimensions in mm
X = fixing dimensions
Wall socket,
4- and 5-pole
Explosion-protected plugs and sockets
63A, GHG 514
1

Technical data

1.1

Plug and socket GHG 514

Marking acc. to 2014/34/EU and standard:
EN 60079-0
ATEX type examination certificate:
Rated voltage:
Rated current:
Back-up fuse:
without thermal protection max. 63 A
with thermal protection max. 80 A gL
Switching capacity AC 3:
Perm. ambient temperature:
Special versions permit deviating temperatures.
Perm. storage temperature in original packing:
**Protection category acc. to EN/IEC 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to EN/IEC 61140:
Cable entry:
wall socket
suitable cables and test torques of the
pressure srew
seel 1+2
min.
1
2
max.
seel 2
min.
1
2
max.
Test torque for screw in thread cable entry (Nm) 7.5
(1)
The maximum clamping area for cables with the seal combination 1+2 can vary according to the type
of cable used.
(2)
When selecting the seal rubber, ensure that the pressure screw can be tightened when carrying out any
future maintenance work on the cable entry.
plug
Supply terminal:
wall socket
plug
Test torques:
Cover screws
Terminals, plug
Terminals, wall socket
Self-cutting screws size 4
Self-cutting screws size 5
Self-cutting screws size 8
Weight:
wall socket
4-pole
GHG 514 44
plug
4-pole
GHG 514 74
wall socket
5-pole
GHG 514 45
plug
5-pole
GHG 514 75
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
EATON's Crouse-Hinds Business
D II 2 G Ex de II C T6
D II 2 D Ex tD A21 IP66 T 80°C**
PTB 00 ATEX 1070
up to 690 V, 50/60 Hz
max. 63 A
up to 690 V / 63 A
-20° C to +40° C (catalogue version)
-20° C to +40° C
IP 66 (catalogue version)
I - is complied with by the devices
(catalogue version)
1x M50 + 1x blanking plug M50
Ø
24.0
(1)(2)
28.0
28.0
(2)
35.0
Ø 19 - 34 mm
Cross section
2 x 4 - 25 mm²
(with cable lugs 1 x 35 mm²)
1 x 4 - 16 mm²
(with cable lugs 1 x 25 mm²)
2.50 Nm
2.40 Nm
3.50 Nm
2.00 Nm
3.00 Nm
3.50 Nm
(catalogue version)
approx. 8.10 kg
approx. 0.75 kg
approx. 8.15 kg
approx. 0.80 kg
690 V VAC
20 A
AC 15
400 V / 6 A
DC 13
24 V / 2 A
Plug,
4- and 5-pole
GB
Nm
6.0
7.0
5.0
7.0
Stripped wire length
19 mm
12 mm
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Crouse-hinds sérieGhg 514

Table des Matières