Installation; Incoming Inspection; Mounting - Siemens SIKOSTART 3RW34 Instructions De Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 83
5

Installation

5.1

Incoming Inspection

1.
2. The carton and packing materials should be retained in case there is a future need to return the soft starter to
If these materials are not used for shipping, claims for shipping damage may be rejected by the freight carrier.
5.2

Mounting

1.
2. Adequate cooling is essential for proper operation. Leave at least 6 inches (150 mm) of clearance above and
3ZX1012-0RW34-1AN1
Heavy equipment
May cause injury or property damage.
To avoid personal injury or soft starter damage, do not
use the unit's cover as a handle when moving and/or
positioning the unit.
If the soft starter is not installed immediately, it should be stored in a clean, dry area where the ambient
temperature is between 0 °C and 70 °C. Avoid storage environments with corrosive atmospheres or high
humidity.
Note: Installation must be performed by qualified personnel as indicated on page 1 of this manual.
Voltage or fire hazard.
Can cause death, serious injury,
or property damage.
To prevent electrical shock or burns, do not leave
foreign objects (wire clippings, metal chips, etc.) either
inside or on top of the soft starter during installation
procedures.
the factory for service or repair. The carton and packing material are especially fitted to protect the soft starter
from shipping damage.
Section 2 of the manual contains soft starter mounting dimensions and data. Air flow through the unit is
vertical, from bottom to top.
Fire hazard
Can cause death, serious injury, or property
damage.
To prevent a fire, the soft starter, especially a
non-fan-cooled unit, must be mounted with its fins in a
vertical direction only. Sideways mounting and
improper ventilating can result in fire.
below the unit to allow unimpeded convection or fan air flow. Wire bending allowance may require more than