AVENTICS | EtherNet/IP™ | R412012728–BDL–001–AC
Table 13:
Load supply assignment for 8x output module, DO8, M12x1, A-coded
Pin
X10
1
0V_U
Q2
2
24V_U
Q1
3
0V_U
Q1
4
24V_U
Q2
6.3.6

FE connection

To discharge EMC interferences, connect the FE connection (2) on the left end
plate to the functional grounding via a low-impedance line.
Recommended cable cross-section: 10 mm
For module extensions (optional): insufficient grounding
If module extensions are used, grounding on the FE connection (2) is insufficient
due to the plastic housing for the module extension.
If using module extensions, also connect the FE connection for each module
extension to the functional grounding via a low-impedance line.
With an HF04-/HF04XF valve block, connect the FE connection (1) on the valve
block to the functional grounding via a low-impedance line.
Assignment
GND reference for power supply 2
24 V supply voltage 1 for outputs O0 to O3
GND reference for power supply 1
24 V supply voltage 2 for outputs O4 to O7
2
CAUTION
57