Notices according to DIN EN 179 and DIN EN 1125
!
Warning!
It is hazardous to modify doors along escape routes: The safety features of this product are an essential
requirement for its conformity with DIN EN 179 and DIN EN 1125. Do not make any changes which are
not described in these instructions.
Unsuitable doors reduce personal safety and intrusion protection: Only approved and technically
correct doors are suitable for installation of the multi-point lock 319N. Prior to the installation of the multi-
point lock 319N, the door must be checked to ensure that it is attached properly and is not warped. The
door must be approved for use of the multi-point lock 319N. Door operating elements may not impede
each other.
The multi-point lock 319N is not approved for use on double acting swing doors.
Unsuitable locks impair personal safety and fire protection: The multi-point lock 319N is suitable for fire
doors and smoke protection doors ("Classification key", page 40). Check whether the door certification
matches the lock. Make sure that the multi-point lock 319N is installed in the appropriate size and with the
correct accessories.
Unsuitable door seals impair personal safety: No function of the lock may be impaired when door seals
are used (such as profile seals or bottom seals).
Broken glass doors may lead to severe injuries: Glass doors or glass parts on doors must be made of
safety glass or composite safety glass.
Unsuitable fastening means reduce personal safety and intrusion protection: Suitable means of fasten-
ing must be used depending in the installation situation and materials of the door.
Incorrect or faulty installation impairs personal safety: The normal installation height for the horizontal
push rod (panic bar) is 900 mm to 1100 mm above the finished floor surface. If children are present in the
majority of the building, the installation high must be reduced accordingly.
The horizontal push rod must be installed such that the greatest possible effective bar length is achieved.
Any lock counterparts or coverings which are provided should be installed in order to ensure conformity
with this European standard.
Limited movement of the door jeopardises personal safety: All blocking elements must be installed
such that the free movement of the door is not impeded. Doors may only be secured with the approved
locks. No additional devices may be installed. Any door closers which are installed may not impair the
actuation of the door by children and infirm persons.