Télécharger Imprimer la page

RIB AA30033 Mode D'emploi page 32

Publicité

Les langues disponibles
  • FR

Les langues disponibles

G
B
turned ON. Therefore, a new command will be needed to close the gate.
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE
FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if photocell
fails or remain engaded for more than 60 seconds, the OPEN, CLOSE, K BUTTON
and PEDESTRIAN commands will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the
programming led.
With the blinking of the programming led, the opening and closing operation are
allowed only with the command button pressed and held. The radio commands
and that of automatic closing, will be excluded, since their use in this mode, is not
allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard
commands that were selected, such as step by step, automatic mode, radio
commands and automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the
safety strips (or photocells) the photocells (or safety strips) still work by
interrupting the operation in progress.
Note 2: the stop command is not to be considered a safety command that can be
bypassed in this mode. Therefore, when pressed or damaged, it will not
allow any movement of the gate.
The dead-man operation is only an emergency operation which must be
activated for a very short period and with the complete installation at sight so
to have a secure and safe control of the system. As soon as possible however,
the failing safety devices must be repaired and activated.
FLASHING LIGHT
Connect the flashing light to J1 flashing light outputs, use flashing lights ACG7059
and bulbs of 40W maximum.
NOTE: This electronic K board can only supply power to FLASHING LIGHTS with
inbuilt flashing circuit.
PRE-FLASHING function
The DIP8 in the ON position enables the pre-flashing, the FLASHING LIGHT starts
T
ROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having positioned the gate in intermediate position, check the correct ignition
of LEDS DL2, DL3, DL4, DL5, DL8.
In case of no ignition of the LEDS, always with gate in intermediate position, check the following and replace any faulty components.
DL2 switched off Faulty Stop button
DL3 switched off Faulty opening limit switch
DL4 switched off Faulty closing limit switch
DL5 switched off Faulty photocells
DL8 switched off Faulty safety edge (In case the edge is not connected, carry out jumper between COM and EDGE)
During functioning with personnel present, with DIP 1 at ON, check that during opening the green DL6 LED switches on and that during closing the red
DL7 LED switches on.
If not, invert clamps V and W on the motor terminal board.
After having carried out the various connections and having supplied
voltage, all the LEDS are switched off.
The gate opens but does not close after the time set.
The gate does not open or close by activating the various OPEN, CLOSE,
K and RADIO buttons.
By activating the K or CLOSE button the gate does not move.
FAULT
working 3 seconds before every movement of the gate.
The DIP8 in the OFF position disables any pre-flashing, the FLASHING LIGHT and
the motor will star at the same time.
OPEN GATE INDICATOR (SIGNAL-COM)
It indicates the gate status: open, partially open or not completely closed.
It switches off only when the gate is completely closed.
During programming, this indicator is active.
NOTE: if button panels or bulbs are in excess, the electronic board logic will be
impaired and operations might stop.
T
ECHNICAL SPECIFICATIONS
- Humidity
- Power voltage
- Frequency
- Maximum board absorption
- Interruptions in electricity supply
- Maximum load of open gate output
- Blinking unit maximum output load
- Current available for photocells and accessories
- Current available on radio connector
- ALL THE PUSH BUTTONS, INPUTS AND COMMANDS CONNECTED TO THE
CONTROL BOARD MUST BE CLE
Check the integrity of fuses F1 and F2. In case of interrupted fuse use only
of adequate value
F2 = 5A
Ensure to have set DIP 3 at ON.
Button K BUTTON always inserted in automatic functioning mode (DIP 6
OFF).
Replace button or switch of the selector switch.
Failed edge self-test => check the connections between electronic board
and edge feeder.
Attention: if not using a feeder for edges, DIP 12 must be at OFF
position.
Faulty safety edge contact.
Faulty photocells contact with DIP 4 OFF.
Fix or replace the relative contact.
Impulse K or CLOSE always inserted.
Check and replace any buttons or micro-switches of the selector switch.
32
32
32
32
< 95% without condensation
230V~ ±10% (120V/60Hz
upon request)
50/60Hz
30mA
100ms
3 W (equal to 1 3W bulb
or to 5 LEDs connected in
series through a resistor of
from 2.2 kΩ)
40W with resistive load
400mA 24Vdc
200mA 24Vdc
SOLUTION
F1 = 100mA.

Publicité

loading

Ce manuel est également adapté pour:

Aa30032Super 3600