Fig. 4: View Atmos GIGA-B
6.2
Electronic module
1.5 ... 7.5 kW:
1
2
3
4
5
8
7
6
11 ... 22 kW:
1 8
6 4
Fig. 5: Electronic module, overview
6.3
Control modes
Installation and operating instructions • Wilo-CronoLine-IL-E, Wilo-CronoTwin-DL-E, Wilo-CronoBloc-BL-E • Ed.01/2024-02
BL-E version
Spiral housing pump with dimensions in accordance with DIN EN 733.
All pump housings are equipped with cast-on pump feet. From motor power ≥ 5.5 kW: Mo-
tors with cast or screwed-on feet.
Installation on a base is recommended for units with a rated power of ≥ 5.5 kW and above.
Depending on the differential pressure and the set control mode, the electronic module reg-
ulates the speed of the pump to a setpoint that can be adjusted within the permissible con-
trol range.
Continuous adaptation of the hydraulic output adapts to the system's changing require-
ments. Changing requirements can be expected especially when thermostatic valves or mix-
ers are used.
The basic advantages of the electronic control are:
Energy saving at the same time as reduced operating costs
Reduced number of differential pressure valves required
Reduction of flow noise
Modification of the pump to changing operating requirements
1
2
3
4
5
6
5
2
7
3
8
7
Available control modes are:
Constant differential pressure (Δp-c)
The control keeps the delivery head constant at the set differential pressure setpoint H
Control is independent of the volume flow and operates until the maximum characteristic
curve is reached.
Fixing points on cover
Operating button
Infrared window
Control terminals
Display
DIP switch
Power terminals (mains terminals)
Interface for IF module
NOTICE
For information on setting the control mode and related parameters, see
section "Operation" and section "Setting the control mode".