Wilo CronoLine-IL-E Notice De Montage Et De Mise En Service page 135

Publicité

Les langues disponibles

Les langues disponibles

11.6.8
Termination
11.7
Menu elements reference
No.
Name
1.0.0.0
Setpoint
2.0.0.0
Control mode
2.3.2.0
Δp-v gradient
3.0.0.0
Pump on/off
Installation and operating instructions • Wilo-CronoLine-IL-E, Wilo-CronoTwin-DL-E, Wilo-CronoBloc-BL-E • Ed.01/2024-02
Disable active
No changes can be made to setpoints or settings. Read-only access to all menu ele-
ments is maintained.
Disable inactive: the elements of the basic menu can be edited (menu elements
<1.0.0.0>, <2.0.0.0> and <3.0.0.0>).
NOTICE
To edit the sub-elements of menu <5.0.0.0>, service mode must also be
activated.
ON
Reset DIP switch 2 to the "OFF" position.
2
The display returns to the status page.
NOTICE
Errors can be acknowledged after a waiting period despite the "access
disable" being active.
In order to establish a clear communication connection between two electronic modules,
both line ends must be terminated.
The electronic modules are factory set for twin-head pump communication and the ter-
mination is permanently enabled. No further settings are required.
This section gives an overview of all items on all menu levels. The menu number and item
type are marked separately, the function of each item is explained. If applicable, there is in-
formation about the setting options of the individual elements.
NOTICE
Some items are hidden under certain conditions. They are therefore
skipped when navigating the menu.
Example: If the external setpoint adjustment in menu <5.4.1.0> is set to
"OFF", menu number <5.4.2.0> is hidden. Menu number <5.4.2.0> is only
visible if the external setpoint adjustment in menu <5.4.1.0> is set to
"ON".
Type Symbol
Values/explanations
Setpoint adjustment/display
±
(for additional information, see section
"Adjusting the setpoint")
Control mode adjustment/display (for addi-
±
tional information, see section "Control
modes" and "Setting the control mode")
Constant speed control
Constant Δp-c control
PID-Control
Setting the gradient of Δp-v (value in %)
ON
±
Pump switched on
OFF Pump switched off
Display conditions
Not displayed for all pump types
en
135