Drive diagnostics with the »Engineer«
Diagnostics tab
All parameters tab
Response to errors
According to the selected response to an error, the state of the internal device control
changes, inhibits the controller, and switches on the LED "DRIVE ERROR":
Response
None
Fault
Trouble
Quick stop by
trouble
Warning locked
Warning
Information
System fault
Danger!
If the fault has been removed, the drive is able to restart automatically from the
"Trouble" device state.
The automatic restart with enabled controller is configured via the code C00142.
Reset of error message
An error message with the response "Fault", "Quick stop by trouble" or "Warning locked"
must be explicitly reset (acknowledged) after the cause of the error has been eliminated.
Device command C00002 = "43: Reset fault"
L
All manuals and user guides at all-guides.com
"Diagnostics" category
Logbook entry
Display under
C00168
EDB94AxH6954 DE/EN/FR/ES/IT 1.0
9400 HighLine | Commissioning guide
Pulse inhibit
Controller inhibit
Acknowledge-
ment required
(after 0.5 s)
is required!