5.4
SHUT-DOWN PROCEDURE
No. ACTION
1
Open OCB
2
Open BCB
3
Open SBCB
4
Open RCB
5
LCD DISPLAY
A30 GENERAL ALARM
A30 GENERAL ALARM
A30 GENERAL ALARM
A30 GENERAL ALARM
BLANK
OPERATING CHECKS
The supply to the load is interrupted.
LED #7 off.
The battery is disconnected from the
rectifier. Led #4 red flashing.
The bypass supply is disconnected. LED
#2 off.
Rectifier and inverter shutdown.
End of shutdown procedure.