Installation and start-up of UPS Keor Hp 400-800kVA
Installation et démarrage de l'UPS Keor Hp 400-800 kVA
Installazione e avviamento UPS Keor Hp 400-800kVA
4.4.1 External manual bypass
Auxiliary contact of the External Manual Bypass Switch on terminals MBY1-MBY2.
A normally open contact has to be connected to the UPS terminals (MBY1-MBY2); when the
contact is closed (see Manual Bypass procedure), the microprocessor will acquire the status of
the contact and shut down the inverter.
4.4.2 Diesel generator (DIESEL MODE)
Auxiliary contact of the Diesel Generator on terminal XD1-XD2.
A normally open contact has to be connected to XD1-XD2 terminals, when the contact is
closed (if diesel mode is enable) the microprocessor will acquire the status of the contact and
the rectifier will reduce the voltage to the value set.
4.4.3 Auxiliary battery contact
Aux battery contact on terminals BAC1-BAC2.
This auxiliary contact is necessary to indicate the position of the isolator (open-closed) and the
fuse status.
4.4.4 Remote emergency power off (EPO)
Aux EPO contact on terminals EAC1-EAC2.
The voltage supply to the loads can be interrupted from a remote location by using this contact
(i.e. for safety requirements). A normally closed contact must be connected to the UPS
terminals (EAC1-EAC2); when this contact is open the static inverter and by-pass switches are
opened so that the output supply is interrupted.
OMD39075 REV. F
41