SIMULTANEOUS USE OF 3 PHASE AND SINGLE PHASE
U
V
W
O
(B)
(B)
(B)
cC
When connecting the load to the single-phase output,
9 Equalize the load (15% or less) among terminals O and U, O
and V, and O and W.
9 Do not load too much on only one phase, or the voltage on
other phases rises too much through the AVR ASSY opera-
tion.
The electrical apparatus may be damaged.
NOTE:
The simultaneous generation of 3-phase and single phase is possible
but the total load should not exceed the following rated output.
G-43201

APPLICATION RANGE

A
AC
B
Power factor
Frequency
C
EDL13000TE
EDL20000TE
EDL26000TE
NOTE:
9 "–" means below.
9 Application wattage indicates when each apparatus is used by itself.
cC
Be sure the total load is within the generator's rated output other-
wise generator damage will occur.
All manuals and user guides at all-guides.com
A
B
Rated current (A)
Power
Source
EDL13000TE EDL20000TE EDL26000TE
220/127V
31.5A
(B)
380/220V
15.2A
779-066
1.0
50Hz
60Hz
–8,000W
–9,600W
–4,800W
–12,400W –14,000W
–7,440W
–16,800W –19,200W –10,080W –11,520W
45.9A
63.0A
23.6A
31.9A
0.6
50Hz
60Hz
–5,760W
–8,400W
– 51 –
同时使用 3 相和单相电源
A 电源
B 额定电流 (A)
告诫:
当把负载连到单相输出端时,
9 9 9 9 9 应使 O 和 U、O 和 V 及 O 和 W 端
子 之 间 负 载 平 衡 ( 等 于 或 小 于
15%) 。
9 9 9 9 9 不要只在一相增加过多负荷,否
则AVR组件运行将使其它相电压
升高过多。
此种情况下可能造成电器损坏。
注意:
同时产生 3 相和单相电流是可能
的, 查总负荷不能超过下示额定输
出。
G-43201
使用范围
A 交流
B 功率因数
C 频率
注意:
9"—"表示最低限度
9 使用电压为使用器械时 , 该器械自
身所需的电压。
告诫:
确认总负荷在发电机相应相电的
额定输出范围之内。否则发电机将会
损坏。