Start the Air + program
The device has an Air + program. When the Air + button is pressed, compressed air is added to the
system for a defined longer period of time, regardless of whether the flushing device is in operation.
Depending on the flushing situation, this can be helpful in order to achieve a longer water pause in the
flushing rhythm.
The Air + program ends automatically after the preset time.
Change the Air + time parameter
The duration of the Air + program can be set between 10 and 90 seconds.
To do this, press and hold the Air + button in standby or during interval operation and at the same
time use the lower + or - button to select the desired value in steps of 0.5 seconds.
After releasing the Air + button, the new time starts automatically!
This Air + value is valid until the device is disconnected from the mains. After switching it on again, it
automatically goes back to 30 seconds.
3.11 Ideal interval time for the compressed air control
The generation of a compressed air-water mixture serves to improve the washing result.
For most heating systems, an interval of 2 seconds pause and 1 second compressed air is ideal.
You can use the control to change the interval time and pause time between 0.0 and 10.0 seconds in
steps of 0.5 seconds and thus adjust the ideal value for your individual flushing situation.