3 INSTALLATION

3.3 General Electrical Connection

The connecting cable conducts the input/output signals and must not be installed in
combination with high voltage or high frequency carrying lines. If a combined installation
cannot be avoided, either keep a min. space of 30 cm (approx. 1 ft) or use coax cables.
When using coax cables observe faultless grounding of the shield. For normal operating
conditions, the input/output signal can be transmitted by a simple cable of 0.75 mm
section.
The power supply must be of good quality (filtrated and regulated).
Note: For EMC purposes,the earth must be connected via the earth lug on the side
of the enclosure. This point must be connected locally to a good earth.
3.4 Electrical connection SE35 Batch
The connections are made via the two 13,5 cable glands.
Remove cover, pull the cable through a PG
13.5 and wire according to following pin
assignment and fig. 4:
1: Binary input 1
2: Binary input 2
3: Binary input 3
4: Binary input 4
5: Indicator lamp output (Transistor Open
Collector)
6: Common (binary inputs and outputs)
7: L+ (12...30 VDC)
8: L-
9: Earth
10: Relay 2
11: Relay 2
12: Relay 1
13: Relay 1
Note: The driver unit supply voltage can be used for the binary inputs and the indicator
lamp output (open collector). In this case the common terminal (6) and the L- terminal (8)
should be connected together.
8035
Main valve
see § 4.4.7
BATCH CONTROLLER SE35
Sensor connection
Fig. 4 Pin assignment SE35 Batch