9.2

Process error messages

Note!
Faults have the highest priority. The associated error code is displayed. A fault is present if the
memory module for writing and reading data is defective or if data could not be read correctly.
9.2.1
Device malfunction
Error code
Cause
E 101
Bus error reading the config/
calibration data after power-up
E 102
Implausible operating data
(checksum)
E 103
Implausible calibration data
E 104
Bus error reading the min/max
data after power-up
E 105
Bus error reading the relay data
after power-up
E 106
Universal card bus error
E 210
Pulse output, pulse buffer over-
flow
E 221
Pump error, digital input 1
E 222
Pump error, digital input 2
Pump error, digital input 3
Pump error, digital input 4
E 290
Number overshoot due to deci-
mal point shift
9.2.2
Incorrect entries
Error code
Description
E 290
The number of digits after the decimal point
cannot be increased due to number overflow of
the dependent parameters.
Effect
Faulty device functioning
Configuration lost
Faulty device functioning
Incorrect min/max values
Incorrect relay data
Faulty universal input functio-
ning
A maximum of 10 pulses are
buffered
Relay goes to failsafe mode
Decimal point position cannot
be altered
Reaction at device
Error code is shown on the display until a key is
pressed.
Trouble-shooting
Remedy
Instrument error, notify Ser-
vice
Perform preset
Instrument error, notify Ser-
vice
Reset min/max values
Reset relay data
Replace universal card, notify
Service
Set the parameters of the pulse
output in such a way that the
maximum frequency is not
exceeded
Acknowledge error via opera-
tion or switching power on/off
Check decimal point position
and number range
79