Commissioning
Function (menu item)
Counts
Dimension
Dec. Y value
Del. points
Show points
Function (menu item)
X value
Y value
76
6.3.9
Linearisation table - LIN. TABLE/M21
The RIA452 can store a table which can be used to linearise the input signal. This table can convert
a level signal to the associated volume for example.
Parameter setting
2..32
XXXXXXXXX
XXXXXXX
XXXXXX.X
XXXXX.XX
XXXX.XXX
XXX.XXXX
No
Yes
No
Yes
6.3.10
Support points of linearisation table - LINPOINTS 1..X/
M23..MXX
Displays the set value pairs of the linearisation table. This menu item is only visible if a linearisation
table was configured under Section 6.3.9 and "Yes" was selected in the "Show points" parameter in
the "LIN. TABLE/M21" menu.
Parameter setting
-99999..99999
-99999..99999
Description
Number of support points needed. At least two points have to be entered.
The technical unit or an arbitrary text for the measured value of the sensor can
be configured here. Max. length 9 characters.
Decimal point position for the Y-values in the linearisation table.
Delete all programmed support points.
Show all programmed support cells.
Description
X-value of the linearisation table. Corresponds to the input value.
Y-value that belongs to the previous X-value. Corresponds to the converted
measured value.
RIA452
Endress+Hauser