Les langues disponibles

Commissioning
Function (menu item)
Ref. integr.
Integr. base
Dec. factor
Factor
Dimension
Dec. total
Totalizer
Reset Total
Function (menu item)
Dec. value
74
6.3.6
INTEGRATION/M18
This function can only be selected if the pulse output option is available in the device.
Parameter setting
Input
Lintab
OFF
sec
Min
hour
day
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
0 ..99999
XXXXXXXXX
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
9999999
No
Yes
Integration function
With this function, the computed value from the linearisation table or that of the analog input can
be numerically integrated to create a totalizer for example.
The totalizer is calculated as follows:
The measuring interval is 0.1 s.
6.3.7
Pulse output - PULSE OUT/M19
All the possible settings for the pulse output can be found in this menu item. This menu item can
only be selected if your device is fitted with this option.
Parameter setting
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
Description
Selects which value should be integrated.
• Input = measured value
• Lintab = linearised measured value
Time basis for integration
Decimal point position of the conversion factor
Conversion factor
The technical unit or an arbitrary text for the measured value of the sensor can
be configured here. Max. length 9 characters.
Decimal point of totalizer
Assign totalizer a default value.
Reset totalizer
!
Note!
Cannot be configured with ReadWin
Description
Decimal point position of the pulse value.
®
2000.