Commissioning

6.1

Function check

Make sure that all post-connection checks have been carried out before you commission your
device:
• See Section 3.3 'Post-installation check'
• Checklist Section 4.3 'Post-connection check'
6.2

Switching on the measuring device

Once the operating voltage is applied, the green LED (= device operating) lights up if no fault is pre-
sent.
• When the device is first commissioned, it is in the status when delivered and uses the default set-
tings for all parameters.
• When commissioning a device already configured or preset, measuring is immediately started as
per the settings. The limit values only switch once the first measured value has been determined.
6.3

Device configuration

This section describes all the configurable device parameters with the associated value ranges and
factory settings (default values).
6.3.1
Analog input - INPUT/M1
All the parameters available for the input can be found under the analog input menu item which is
marked as INPUT in the device.
Parameter setting
Off
4 - 20 mA
0 - 20 mA
*
0 - 5 mA
*
0 - 100 mV
*
0 - 200 mV
*
0 - 1 V
*
0 - 10 V
*
± 150 mV
*
± 1 V
*
± 10 V
*
± 30 V
*
Type B (IEC584)
*
Type J (IEC584)
*
Type K (IEC584)
*
Type L (DIN43710)
*
Type L (GOST)
*
Type N (IEC584)
*
Type R (IEC584)
*
Type S (IEC584)
*
Type T (IEC584)
*
Type U (DIN43710)
*
Type D (ASTME998)
*
Type C (ASTME998)
Description
Selects the signal type of the connected sensor. Parameters marked * can only be
selected with the universal input option.
Commissioning