Process transmitter
3. Allocating the volume to the differential pressure using the
linearisation table of the mathematics channel. Special tank
forms can be described using a further 18 linearisation points:
Menu group
Mathematics channel
MATH
(differential pressure
[bar]
3
volume [m
])
TABM
Linearisation table
NOM02
Lin. point 2
.
.
.
.
NOM19
Lin. point 19
Further parameters in order to complete the measurement
point, such as measured value display on the unit, analogue
value output and set point alarm monitor:
Menu group
DISPL
Display
OUT1
Analogue output 1
(Head pressure [bar])
OUT2
Analogue output 2
3
(volume [m
])
LIM1
Limit 1
(Minimum monitoring of
head pressure)
LIM2
Limit 2
(Maximum monitoring of
volume)
64
Parameter
Curve
X-value lin. point 1
X-value last lin. point
Y-value decimal point
Y-value lin. point 1
Y-value last lin. point
Number of linearisation points
Input value
Output value
.
.
Input value
Output value
Parameter
Reference value
Reference value
Output range
Analogue output 0% scale
Analogue output 100% scale
Reference value
Output range
Analogue output 0% scale
Analogue output 100% scale
Reference value
Operating mode
Switch threshold
Hysteresis
Reference value
Operating mode
Switch threshold
Hysteresis
Set-up
MCURV
TABLE
MSCLO
000,00
MSCHI
002,50
MDIDP
9999,9
MDILO
0000,0
MDIHI
2020,0
COUNM
Number and
X2
values
Y2
independent
of tank
geometry
X2
Y2
Set-up
DISOW
MATH
OREF1
IN 2
RANG1
4-20
OLO1
000,00
OHI1
001,00
OREF2
MATH
RANG2
4-20
OLO2
0000,0
OH21
2020,0
LREF1
IN 2
MODE1
MIN-
SETP1
000,30
HYST1
000,05
LREF2
MATH
MODE1
MAX
SETP1
1900,0
HYST1
0005,0