Analogue Outputs - Endress+Hauser RMA 422 Mise En Service

Masquer les pouces Voir aussi pour RMA 422:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Process transmitter

5.4 Analogue outputs

The following addresses are only available if the
unit is fitted with the analogue output option.
Parameter
* Reference value
Selection of signal source of
the analogue output value
* Output range
Select current or voltage
output with 0% and 100%
values.
* Scale
analogue output
Allocation of numeric display
value to the 0% analogue
output value.
*Scale
analogue output 100%
Allocation of numeric display
value to the 100% analogue
output value.
For inverted signal output the 100%value must be smaller than the 0% value
* Fault condition
Definition of the output signal
in fault condition. These are
sensor cable open circuit or
unit internal fault
* Simulation
voltage/current
Dependent whether current
or voltage output is set, a
number of values are offered
that can be transmitted to the
output
Once this address is left the output is automatically set to
The red LED flashes during active simulation!
54
Setting up selections
OREF1
OREF2
/
Selection range:
IN1
:
Process value ch. 1
IN2
:
Process value ch. 2
MATH
: Process value maths.
RANG1
RANG2
/
4-20 mA, 0-20 mA, 0-10 V
OLO1
OLO2
0%
/
Selection range:
Display value 0% (
Display value 100% (
OHII
OHI2
/
Selection range:
Display value 0% (
Display value 100% (
FAIL1
FAIL2
/
HOLD
Output of last
valid measurement
MIN
Output 0% value,
at 4-20 mA: 3.5 mA
MAX
Output 100% value,
at 4-20 mA: 22 mA
SIMU1
SIMU2
/
OFF
Simulation is switched
off, the output value is
proportional to the
measured value.
Voltage output:
0,0V
5,0V
,
,
Curent output:
0,0MA, 3,6MA, 4,0MA, 10,0MA,
12,0MA, 20,0MA, 21,0MA
Default
settings
IN1
4-20
0,0
DILO
) to
DIHI
)
100,0
DILO
) to
DIHI
)
HOLD
OFF
10,0V
OUT1
/
OUT2
Actual
setting
OFF
.