– Level 10 m
– Numeric display should show 1500 (m
– Bar graph should show 100%
– 20 mA should be present at the analog output
1
Sensor
X
signal
value
(mA)
4,0
Display
Y
value
value
3
(m
)
0
The following parameters must be configured for the example above:
Menu
LIN. TABLE / M 21
LINPOINTS 1 to 10 / M23 to 32
ANALOG OUT / M 3
DISPLAY / M 2
!
Note!
®
ReadWin
2000 operating software supports the generation of a tank linearization table.
Here you can find a tank linearization generator which you can use to generate the linearization
table for standard and customer-specific tanks.
Endress+Hauser
2
3
4
X
X
X
value
value
value
4.32
4.64
4.96
Y
Y
Y
value
value
value
20
50
85
Function (menu item)
Counts
Dimension
Show points
Each point
Each X value
Each Y value
Ref. num
Out range
Fail mode
Fail value
Ref. num.
Ref. bargraf
3
)
Point
5
6
7
X
X
X
value
value
value
5.28
5.6
5.92
Y
Y
Y
value
value
value
115
160
210
Setting value
Number of support points (10)
Dimension of lin. value (m
Display support points (Yes)
Use point (Used)
X-value (as in table above)
Y-value (as in table above)
Output value (lin tab)
Signal type (0-20 mA)
Failsafe mode (const)
Value in event of error (21 mA)
Reading on display (lin. table)
Signal source for bar graph (lin tab)
Commissioning
8
9
10
X
X
X
value
value
value
6.24
6.56
20.0
Y
Y
Y
value
value
value
280
400
1500
3
)
135