Endress+Hauser RIA452 Mode D'emploi page 111

Masquer les pouces Voir aussi pour RIA452:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

RIA452
Function
(menu
item)
Fail mode
Hold
const
Min
Max
Fail value
0..999.99
0.00
Simu mA
OFF
0.0 mA
3.6 mA
4 mA
10 mA
12 mA
20 mA
21 mA
OFF
Simu V
0.0 V
5.0 V
10.0 V
Endress+Hauser
Parameter setting
Description
Output value if a sensor or device error occurs.
• Hold = last valid value
• Const = freely selectable value
• Min = output value 3.5 mA for 4 to 20 mA,
otherwise 0 V or 0 mA
• Max = output value 22.0 mA for 0/4 to 20 mA,
otherwise 1.1 V or 11 V
The freely selectable value for "Fail mode = Const" can
be set here.
Current output: 0 to 22 mA
Voltage output: 0 to 11 V
Simulates the current output and outputs the selected
current at the output, regardless of the input value.
Is automatically set to OFF when the Simu mA menu
item is exited.
Simulates the voltage output and outputs the selected
voltage at the output, regardless of the input value.
Is automatically set to OFF when the Simu V menu
item is exited.
Commissioning
111

Publicité

Table des Matières
loading

Table des Matières