Commissioning
6.3.4 Digital input - DIGITAL INP./M5
The settings for the digital status inputs, e.g. for monitoring pumps, starting/stopping the
counter or resetting the min/max-value memory are grouped in this section.
!
Note!
– The digital inputs 1 to 4 are permanently assigned to relays 1 to 4 in the PUMP function.
Relay 1 is monitored by digital input 1, relay 2 by digital input 2 etc.
– When the "Batch" function is used, digital input 1 is permanently assigned to a preset value
count function. Configuration for this digital input is then not possible.
Function
(menu
item)
Off
Function
Pump
Res Tot. (*)
Start/Stop (*)
Res MinMax
Level
Low
High
Sampl. time
0..99
0
112
Parameter setting
Description
Function of the selected digital input.
• Off
• Pump = pump monitoring (see Pump monitoring
function)
• Res Tot. = reset the totalizer*
• Start/Stop = start or stop the totalizer*
• Res MinMax = reset the min/max memory values
!
Note!
Parameters marked with an asterisk (*) are only
available for the pulse output option if this function has
been configured.
Selects the side for evaluation.
• Low = descending side
• High = increasing side
Defines the time (in seconds) within which pump
feedback at the digital input is to be expected. If there
is no feedback within the defined time, an error
message is generated and a second pump is activated if
more than one pump is available.
!
Note!
The sampl. time setting is used to specify the
monitoring behavior of the digital input!
Sampl. time = 0 means fault monitoring
Sampl. time <> 0 means operation monitoring
RIA452