Function
(menu
item)
Sw. delay
0..99
0
Sw. period
0..999
0
Runtime
Count
No
Reset
Yes
Simu relay
Off
Low
High
Endress+Hauser
Parameter setting
Description
The starting time for 24-hour counting can be selected
with Sw. delay. Every time the instrument is reset, the
process of measuring 24 hours and the delay time is
restarted.
Example see Page 44
Limit value is activated cyclically every 24 hours for 0
to 999 seconds. The activation is delayed by [Sw.delay]
hours by changing the hour value (example
see Page 44).
Displays the run time of the connected device, e.g.
pump, in hours [h].
Records the switching frequency of the limit value.
Resets the run time and switching frequency for this
limit value.
Simulation of the selected limit value. Is automatically
set to Off when the menu item is exited.
Commissioning
117