Technical data

General data and operating conditions

Field
Communication profile
Communication medium
Network topology
Max. number of devices
DeviceNet device
Baud rate [kbit/s]
Achievable bus cable length
External voltage supply
Ambient conditions
Climatic conditions
Transport 2 K3 acc. to IEC/EN 60721−3−2
Operation 3 K3 acc. to IEC/EN 60721−3−3
Degree of pollution
Enclosure
Connections
X3/
V+
7
39
28
20
EDK82ZAFVC001 DE/EN/FR 2.0
Values
DeviceNet
DIN ISO 11898
Line terminated at both ends (R = 120 Ohms)
63
Slave
125, 250, 500
Depending on the cable used, see ^ 48
See ^ 44
Storage 1 K3 acc. to IEC/EN 60721−3−1
2 acc. to IEC/EN 61800−5−1
IP20
External DC voltage supply of the function module:
+24 V DC ±10 %, max. 80 mA
The current flowing via terminal V+ during looping through of
the supply voltage to other devices, is to amount to a
maximum of 3 A.
Reference potential 1
Reference potential 2 of the controller inhibit (CINH) at X3/28
Controller inhibit
l
Start = HIGH (+12 V ... +30 V)
l
Stop = LOW (0 V ... +3 V)
Input resistance: 3.3 k
+ 20 V internal for CINH, reference potential 1, load capacity:
I
= 30 mA
max
l
General data and operating conditions
− 25 ... + 60 °C
− 25 ... + 70 °C
− 20 ... + 60 °C
W
Technical data