Electrical installation
Specification of the transmission cable
The devices are connected to the bus system using a fieldbus cable according to the
TM
DeviceNet
specification (DeviceNet Adaption of CIP, Edition 1.1, Volume Three).
Companies like Belden Wire & Cable, Olflex Wire & Cable, C&M Corp. and Madison Cable
produce DeviceNet
)
Note!
Use the Thin" cable to wire the function module
Features of the Thin" cable according to DeviceNet specifications
General features
Configuration
Total shielding
Drain wire
Outer diameter
Roundness
Jacket marking
Spec. DC resistor (braid, tape, drain)
Certifications (U.S. and Canada)
Bend radius
Ambient operating temperature
Storage temperature
Pull tension
42
TM
Thick" and Thin" cables.
Two shielded symmetrical cables with a common axis and drain wire in
the centre
65% coverage
AWG 36 or min. 0.12 mm tinned braid (individually tinned)
Copper 22 min.; min. 19 cores (individually tinned)
6.096 mm (min.) to 7.112 mm (max.)
Radius deviation must be within 20% of 0.5 outer diameter
Vendor name & part no. and additional markings
10.5 Ohm/1000 m (nominal at 20°C)
NEC (UL), CL2 (min.)
20 x diameter (installation) / 7 x diameter (fixed)
−20°C to +70°C at 1.5 Ampere; derate current linearly to zero at 80°C
−40°C to +85°C
289.23 N
max
l
^ 42
.
EDK82ZAFVC001 DE/EN/FR 2.0