4
Electrical installation
Max. possible bus cable length
The following bus cable lengths are possible in dependence on the baud rate and the cable
used:
Baud rate
125 kbits/s
250 kbits/s
500 kbits/s
When using both, Thick" and Thin" cables, the maximum cable lengths are to be selected
according to the baud rate:
Baud rate
125 kbits/s
250 kbits/s
500 kbits/s
48
Thin Cable
100 m
Bus cable length
L
= 500 m
= L
max
thick
L
= 250 m
= L
max
thick
L
= 100 m
= L
max
thick
l
Thick Cable
500 m
250 m
100 m
+ 5 L
thin
+ 2.5 L
thin
+ L
thin